Wecon LX3V-4TC Analog Input PLC Module

Wecon LX3V-4TC Analog Input PLC Module



  • Description
  • Additional Information

ItemSpecification
Dielectric withstand voltage500V AC, 1min (between all terminals and ground)
Analog circuits24V DC ± 10%, 55mA
Digital circuits5V DC, 90mA (internal power supply from the main unit)
Centigrade (°C)/Fahrenheit (°F)

Both °C and °F are available by reading the appropriate buffer memory(BFM).

Input signal

Thermocouple: Type K or J (either can be used for each channel), 4 channels

Rated temperature range(°C)Type K:-100℃ to +1200℃        Type J:-100℃ to +600℃
Rated temperature range(°F)Type K:-148℉to +2192℉         Type J:-148℉ to +1112℉
Digital output(°C)Type K:-1000 to 12000           Type J:-1000 to 6000
Digital output(°F)Type K:-1480 to 21920           Type J:-1480 to 11120
Digital output12-bit conversion ,save as complement of 2 in 16 bits
Overall accuracy± (0.5% full scale +1°C)

Freezing point of pure water 0°C / 32°F

Conversion speed(240ms ± 2%) × 4 channels (unused channels are not converted)
CE CertificationCE marked