| Model | Channels | Resolution | Functionality |
| LX3V-4TC | 4 | 14 bits | Analog thermocouple inputs |
| LX3V-4LTC | 4 | 14 bits | Analog thermocouple inputs, with PID Control |
Specification
| Item | LX3V-4TC | LX3V-4LTC | LX3V-8iTC (out of production) | ||
| Dielectric withstand voltage | 500V AC, 1min (between all terminals and ground) | ||||
| Analog circuits | 24V DC ± 10%, 70mA | 24V DC ± 10%, 50A | |||
| Digital circuits | 24V DC, 35mA (internal power supply from the main unit) | ||||
| Centigrade (°C)/Fahrenheit (°F) | Both °C and °F are available by reading the appropriate buffer memory (BFM). | ||||
| Input signal | Thermocouple: Type K or J (either can be used for each channel), 4 channels | Thermocouple: Type K,J,T,E,N,B,R,S(either can be used for each channel), 8 channels | |||
| Rated temperature range(°C) | Type K: -100℃ to +1200℃ Type J: -100℃ to +600℃ | ||||
| Rated temperature range(°F) | Type K: -148℉to +2192℉ Type J: -148℉ to +1112℉ | ||||
| Digital output(°C) | Type K: -1000 to 12000 Type J: -1000 to 6000 | ||||
| Digital output(°F) | Type K: -1480 to 21920 Type J: -1480 to 11120 | ||||
| Digital output | 12-bit conversion, save as complement of 2 in 16 bits | ||||
| Overall accuracy | ± (0.5% full scale +1°C) | ||||
| Freezing point of pure water 0°C / 32°F | |||||
| Conversion speed | (240ms ± 2%) × 4 channels (unused channels are not converted) | ||||
| CE Certification | CE marked | ||||